METHOD
STATEMENT |
|
|
-
Drill
16mm diameter holes at 100-500mm intervals along
the side of the crack or joint, at a 45º angle in order that the path of the crack
or joints intersected in the center of the
concrete slab or wall. The distance between
holes will depend on the size of the crack or
joint to be injected.
-
Insert
the mechanical packers into the 16mm diameter holes
and tighten securely.
-
Using
a clean and dry bucket, pour in the Foam
Grout or Foam Flex XP-1 to the desired amount.
Add the Foam LYST (catalyst) gradually -
average recommended at 5% ( 5 : 100 ). Stir
well. Increase the dosage if rapid curing is
required.
-
Commence
injection using either a FG GROUT PUMP
(manual) or YK-MES1000/2000 electrical grout pump,
ensuring that the crack is filled. The material
must be visible during the initial set stage (yellow
coloured expanding foam). Always return to
previously injected packers and re-inject to
ensure that the material is completely
compacted.
In the event of filling vertical cracks or
joints, commence grouting from the bottom. In case of
horizontal cracks or joints, begin from either
side.
Inexperience operating the pump may cause it to
clog. Increase operating speed may be required
if a large amount of catalyst is used.
-
Allow
the grout to cure for 24 hours before removing
all packers. Exposed, Solidified grout will be
visible. Plus all holes with a suitable mortar.
-
It
is recommended to flush the machine with non-flammable solvent after used.
|
|
 |
 |
|
Water
Leakage (Before Repair) |
|
|
|
|
|
|
|
|
|
 |
 |
|
Insert
Packer and Slot-in Connector |
|
|
|
|
|
|
 |
 |
|
INJECT
with Foam Grout or XP-I |
|
|
|
|
|
|
|
Back
| Top^
| Next |
|
|
|
|